The LabGard ES 435 Biological Safety Fume Hood is designed to standard NFPA-45 and UL 1805. Exterior outlets, valves, and fire rated HEPA filters ensure a proper environment for use of flammable liquids, chemicals, isotopes, and radionuclides.


NSF/ANSI 49   UL Classified Canada United States Listing

Part #: NU-435

Features

The LabGard ES 435 Biological Safety Fume Hood is designed to standard NFPA-45 and UL 1805. Exterior outlets, valves, and fire rated HEPA filters ensure the proper environment for use of flammable liquids, chemicals, isotopes and radionuclides.

Model NU-435 has been replaced by model NU-565

Specs


Catalog Number

Catalog Number

NU-435-400

Nominal 4 foot (1.2m)

NU-435-600

Nominal 6 foot (1.8m)

Performance Specifications

  1. Personal Protection

  2. Product Protection


ASHRAE-110 NSF/ANSI 49


ASHRAE-110 NSF/ANSI 49

NSF Std. No. 49 Class

Class II, Type B2

Class II, Type B2

Style of Fume Hood

Bench Top/Console w/Base Stand/

Storage Cabinet

Bench Top/Console w/Base Stand/

Storage Cabinet

Fume Hood Construction

All Welded Stainless Steel 16GA,

Type 304 Pressure Tight Design

All Welded Stainless Steel 16GA,

Type 304 Pressure Tight Design

Diffuser for Air Supply (Metal)

Non-Flammable

Non-Flammable

HEPA Filter Seal Type, HEPA Type: Supply Filter-99.99% Eff. on 0.3 Microns

Exhaust Filter-99.99% Eff. on 0.3 Microns


HEPEX Seal, UL Class I

Neoprene, Spring loaded, UL Class 586


HEPEX Seal, UL Class I

Neoprene, Spring loaded, UL Class 586

Fumigation per NIH/NSF Procedure

Yes

Yes

Standard Services:

Remote Controlled Valves ** Duplex Outlet


Two, Right Sidewall One, Left Front Faring


Two, Right Sidewall One, Left Front Faring

Optional Services:

Remote Controlled Valves** Standard/Cup Sinks


Up to 3 ea. Sidewall

Left or Right Work Surface


Up to 3 ea. Sidewall

Left or Right Work Surface

Fume Hood Size Inches (mm): Height (Fully Assembled) Height (Minimum for Transport) Width

Depth (with Control Center)


61 (1549)

61 (1549)

53 5/8 (1362)

32 7/8 (835)


61 (1549)

61 (1549)

77 5/8 (1972)

32 7/8 (835)

Work Access Opening Inches (mm): Standard Opening Height

Standard Inflow Velocity


8 (203)

105 FPM (.53 m/s)


8 (203)

105 FPM (.53 m/s)

Work Zone Inches (mm): Height

Width

Depth


25 1/2 (648)

46 3/8 (1178)

23 1/2 (597)


25 1/2 (648)

70 3/8 (1788)

23 1/2 (597)

Viewing Window Inches (mm): Standard is Tempered Sliding Glass

Hinged Tempered Glass (optional)

1.0 (25) Closed 18 1/2 (470) Open

8 (203) Access Opening

1.0 (25) Closed 18 1/2 (470) Open

8 (203) Access Opening

Certification Exhaust Value CFM/CMH

Concurrent Balance Value CFM/CMH +

754/1281

785/1334

1100/1867

1250/2124

Plant Duct Static Pressure Eng/Metric

1.7” w.g./43mm w.g.

1.8” w.g./46mm w.g.

Heat Rejected, BTU, Per Hour

474

584

Electrical: Volts, AC 60 Hz

++Amps: Blower/Lights Amps: Duplex

Amps: Total

12 ft. Power Cord (one)

U.L. Classified 115, 60Hz

2.1

3

8

14 GA - 3 Wire, 15A

U.L. Classified 115, 60Hz

2.6

3

10

14 GA-3 Wire, 15A

Crated Shipping Weight:

Net Weight

570 lbs./259 kg.

520 lbs./236 kg.

760 lbs./345 kg.

710 lbs./322 kg.

**Remote controlled valve handles project through front faring. Decorative side panels are present to cover plumbing.

+Concurrent Balance Value shall be used for design and balance exhaust/supply HVAC requirements.